| Property |
Test Method |
HySSIL™ Test Results |
Comments |
| Bulk density |
Samples cut from pilot
sized panels |
After de-moulding 1,500
kg/m3
28 days standard: 1,450 kg/m3
Oven dried: 1,250 kg/m3
|
|
| Strength* |
Flexural tests on 100x100x400mm prisms cut from pilot sized
panels
Compressive strength results obtained from ISO type test
on flexural test prisms
|
Standard curing
Flexural: 3.3-3.5 MPa @ 28 days
Compressive: 17-20 MPa @ 28 days
Heat accelerated curing
Flexural: 2.8-3.2 MPa @ 28 days
Compressive: 14-17 MPa @ 28 days
|
|
| Elastic modulus |
Tested on 100x100x200mm fog cured prisms |
11 GPa |
HySSIL approximately 50% of 20 MPa concrete with density of 2,500 kg/m3 |
| Drying shrinkage |
Measured from stainless steel gauge studs embedded through full thickness on longitudinal axis of 600x1,800x100mm panel |
500 microstrain @ 56 days
600 microstrain @ 1 year#
700 microstrain ultimate#
|
AS3600 typical 30 year design shrinkage for internal environment
~ 860 microstrain
|
|
Water sorptivity
|
400x170x100mm slabs subjected to 50mm hydro-static head in
rain machine.
Sample pre-dried for 21 days before testing.
|
d24=8-13mm@28 days
|
Exceeds requirement eg for AS3600 exposure classification
B2.
|
|
Thermal conductivity
|
Guarded hot box method complying with ASTM C 518,AS/NZS 4859
|
0.35-0.6 W/mK for lab dry densities ranging from 900-1,400
kg/m3
|
Thermal conductivity of normal density concrete typically
ranges between 1.5 to 2.5 W/mK
|
|
Fire resistance
|
Fire curve as per AS1530.4 on 1m2 wall panel area
Raw joints with no fire retardant sealing
|
For 75mm thick panel
2.5 hours to insulation failure
1.2 hours to joint failure
|
Panel tests with raw joints
- no fire retarding joint seal
|
|
Structural bending strength
|
600x1, 800x100mm panels reinforced with single F62 mesh
at centerline
4 point bending at 540mm centres
|
Serviceability bending capacity up to 1.5MPa
|
- Up to 3 times less than N40 concrete
- Ability to resist ultimate strength and serviceability limit
state wind loads for 3m spans
|
|
Pull-out strength
|
Tests on No 14 Tapcon threaded fastener and D6058 Dynabolt
|
3 kN for Tapcon
2 kN for Dynabolt
|
Capable of fixing 200kg/linear metre loads. (eg: cabinets
and contents)
|
|
Impact strength
|
Hard impact tests and measurement on diameter of indentation
0.5 and 1.0kg balls dropped from heights of 400mm and 800mm
|
Diameter of indentation between 8-15mm
|
Impact resistance of N40 normal density concrete panels is
about 30% better than HySSIL
|